Ex power supply 5420B
2 channels
5-port 3.75 kVAC galvanic isolation
Output voltage > 18 V to I.S. area
Active current loop detection
Universal supply by AC or DC
Application
- Voltage supply with safety barrier for the supply of equipment mounted in hazardous area.
- Voltage supply with failsafe detection of active current loop from 2-wire transmitters mounted in hazardous area.
Technical characteristics
- PR5420B has a relay with change-over contacts available in the safe area. When the loop current is within the defined limit, the relay is ON.
- Supply and outputs are floating and galvanically separated.
Mounting / installation
- Mounted vertically or horizontally on a DIN rail. Up to 84 channels per meter can be mounted.
Note
- Not suitable for new installations requiring certification to the latest ATEX standards - see ATEX certificate DEMKO 99ATEX126256 and EU Declaration of Conformity for details.
Product Documents:
- Datasheet
- User Manual (English)
- User Manual (Russian)
- PR Electronics Temperature Brochure
- PR Electronics Product Guide