Specification
Unique, robust IP66, IP67 (NEMA Type4X) panel mount front enclosure made of die cast aluminum, allowing even big jets of water and total immersion
- Displays flow rate, total, accumulated total and flow rate alarm messages.
- Two alarm values can be entered: low and high flow rate alarm.
- Selectable on-screen engineering units; volumetric or mass.
- Large 17mm (0.67″) digits for flow rate or total.
- Ability to process all types of flowmeter signals.
- Auto backup of settings and running totals.
- Ambient temperature: -40°C to +80°C (-40°F to 176°F).
- Red flashing LED backlight in case of a flow rate alarm.
- Easy configuration with clear alphanumerical display.
- Aluminum DIN front panel of 144 x 72mm (5.67” x 2.83”) according to DIN 43700 / IEC 61554.
- Various accessories are available for this product.
- The D013 fits in flow measurement applications where continuous flow rate monitoring is important without signal re-transmission.
- The D-Series is a DIN-sized display and the better alternative for your existing, not waterproof, front panel mount indicators in extreme weather outdoor applications or e.g. in food industries where working environments are often cleaned with powerful water jets.
Signal Inputs
Flow meter input :
Pulse type inputs: Reed-switch, NAMUR, NPN/PNP pulse, Sine wave (coil), active pulse signal.
(0)4 – 20mA.
0 – 10V DC.
Signal outputs
Pulse outputs
None
Alarm outputs
Function: Configurable alarm output for high, low or both combined flow rate alarms. Type: One passive signal output, an active signal output or a robust, highly isolated (NO/NC) relay.
Analog outputs
None
Supply
Power Supply
Basic: 8 – 30V DC (no real sensor supply).
Long life Lithium battery.
4 – 20mA input Loop-powered.
24V AC/DC + sensor supply.
115 – 230V AC + sensor supply.
Sensor Supply
1.2 / 3V DC.
8.2, 12 & 24V DC.